XDR-240R DIN Rail Power Supply | 12V / 24V / 48V (LED Power Supply)
240W high-efficiency industrial DIN rail power supply with a compact 30mm-wide metal enclosure. Available in 12V, 24V and 48V DC outputs, featuring universal 90–264Vac input, built-in active PFC and efficiency up to 95%. Optional DC OK relay contact and redundancy function for industrial power systems. 3-year warranty.
- 30mm ultra-slim metal enclosure
- 12V / 24V / 48V output options
- Output power up to 240W
- Universal AC input: 90–264Vac
- Built-in active PFC, power factor 0.95
- High efficiency up to 95%
- Optional DC OK relay contact
- Optional redundancy function
- Supports parallel connection of two power supplies with redundancy option
- 3-year warranty
Availability: In stock
XDR-240R Slim Industrial DIN Rail Power Supply – 12V / 24V / 48V
The HYRITE XDR-240R series is a high-efficiency single-output industrial DIN rail power supply, designed for industrial control cabinets, automation equipment and demanding indoor applications.
Featuring a slim 30mm-wide metal enclosure, universal AC input from 90 to 264Vac and built-in active Power Factor Correction (PFC), the XDR-240R delivers reliable DC power with efficiency of up to 95% and a power factor of 0.95. It is available in 12V, 24V and 48V output versions and supports standard TS35/7.5 and TS35/15 DIN rail mounting.
Optional DC OK relay contact and redundancy functions are available for industrial systems requiring output status monitoring and redundant power configurations.
Model Selection
| Model | Output Voltage | Output Current | Rated Power |
|---|---|---|---|
| XDR-12U240R | 12V DC | 16A | 192W |
| XDR-24U240R | 24V DC | 10A | 240W |
| XDR-48U240R | 48V DC | 5A | 240W |
Key Features
- Ultra-slim 30mm-wide metal enclosure for space-saving installation.
- Universal AC input voltage: 90–264Vac.
- Built-in active Power Factor Correction (PFC), with a power factor of 0.95.
- High efficiency of up to 95%.
- Three output voltage options: 12V, 24V and 48V DC.
- Optional DC OK relay contact for output status monitoring.
- Optional redundancy function for parallel connection of two power supplies.
- Low leakage current, specified as less than 0.5mA at 240Vac in the feature description.
- Comprehensive protection against short circuit, overload, overvoltage and overtemperature.
- Compatible with TS35/7.5 and TS35/15 DIN rails.
- 100% full-load burn-in testing.
- LED indicator for power-on status.
- High reliability with a 3-year warranty.
- Designed to comply with IEC/EN/UL 62368-1 safety requirements.
Input Specifications
| Input Voltage | 90–264Vac / 127–370Vdc |
| Frequency Range | 47–63Hz |
| Power Factor | 0.95 |
| Efficiency | 93.5% @ 12V / 94.5% @ 24V / 95% @ 48V |
| AC Input Current | As specified: ≥3A @ 115Vac / ≥1.5A @ 230Vac |
| AC Inrush Current | 23A @ 115Vac / 45A @ 230Vac |
| Leakage Current | Specified as ≥0.5mA @ 240Vac in the electrical parameter table; see datasheet note. |
Output Specifications
| Parameter | 12V | 24V | 48V |
|---|---|---|---|
| Output Current | 16A | 10A | 5A |
| Rated Power | 192W | 240W | 240W |
| Voltage Tolerance | ±1% | ±1% | ±1% |
| Voltage Adjustment Range | 12–14V | 24–28V | 48–55V |
| Ripple & Noise (Max.) | 150mV P-P | 150mV P-P | 200mV P-P |
| Hold-up Time (Typ.) | 14ms @ 230Vac / 14ms @ 115Vac | ||
Protection Functions
- Overload Protection: 130%–160% of rated power. Hiccup mode with automatic recovery after the fault condition is removed.
- Short Circuit Protection: Hiccup mode with automatic recovery after the fault condition is removed.
- Overvoltage Protection: Shunt-down protection, recovery after power is restarted.
- Overtemperature Protection: Shunt-down protection with recovery after the temperature drops.
DC OK Relay Contact (Optional)
The optional DC OK relay contact provides an indication of the DC output status for external monitoring and control systems.
| Contact Closed | Power ON / DC OK |
| Contact Open | Power OFF / DC Fail |
| Maximum Contact Rating | 30V / 1A, resistive load |
Redundancy Function (Optional)
The optional built-in redundancy function supports parallel connection of two single power supplies.
When two power supplies are connected in parallel, the maximum load must not exceed the rated power of either individual power supply. This configuration is intended for power supply redundancy rather than increasing the total rated output power.
Environmental & Mechanical Specifications
| Operating Temperature | -30°C to +70°C (Refer to derating curve) |
| Operating Humidity | 20–90% RH, non-condensing |
| Storage Temperature | -40°C to +85°C |
| Storage Humidity | 10–95% RH |
| Dimensions (W × H × D) | 30 × 125.1 × 110mm |
| Net Weight | 0.6kg |
| DIN Rail Compatibility | TS35/7.5 or TS35/15 |
| MTBF | ≥300,000 hours (MIL-HDBK-217F, 25°C) |
| Warranty | 3 Years |
Safety & EMC Compliance
Safety standards: UL 62368-1, EN 62368-1 and GB 4943.1.
EMC standards include EN 55032 (CISPR 32), FCC Part 15, CISPR 22, GB 9254.1, EN 61000-3-2, EN 61000-3-3, EN 55035 and EN 61000-4 series immunity standards.
Harmonic current compliance: EN 61000-3-2, Class A.
Installation Guide
- Designed for indoor installation.
- Ensure the power supply is properly grounded before installation and operation.
- Maintain adequate ventilation and heat dissipation. Avoid installation in sealed, high-temperature environments or near flammable and explosive materials.
- Do not block the ventilation openings of the power supply.
- Keep the connection cables between the power supply and load as short as possible to minimize voltage drop.
- Tighten all terminal connections properly to prevent overheating caused by poor contact.
- Refer to the loading and ambient temperature derating curves when selecting the operating load.
Request a Quote
Looking for a high-efficiency DIN rail power supply with active PFC and optional redundancy and DC output monitoring?
Contact HYRITE Lighting for product specifications, pricing and technical support. Please specify your required output voltage, model, quantity and whether you need the optional DC OK relay contact or redundancy function, so we can recommend the appropriate solution for your application.
| Model no. | XDR-12U240R / XDR-24U240R / XDR-48U240R |
|---|---|
| Input voltage | 90–264VAC / 127–370VDC |
| Input Voltage System | 100-240VAC |
| Max. output power | 192W(12V) / 240W(24V, 48V) |
| Output type | Constant voltage |
| Power Factor | High PF>0.9 |
| Output voltage | 12V / 24V / 48V DC |
| Max. output current | 16A (12V) / 10A (24V) / 5A (48V) |
| Installation | Indoor |
| Protection | Overload, Short circuit, Overheat, Over voltage |
| Dimensions(L*W*H) | 30 × 125.1 × 110mm (W × H × D) |
| Weight(kg) | 0.6000 |